7.5.2
Importing ICD or CID files
1.
Select an existing IED to import IEC 61850 files.
2.
From the
Files of type
list, select the file type of IEC 61850 to be imported (ICD
or CID).
The
SCL Import Option
dialog box opens.
3.
In the
SCL Import Option
dialog box, select how the file is to be handled during
the import.
GUID-ADF60975-2AD7-47CF-AD26-37094ACEA4F0 V1 EN
Figure 84:
SCL Import Options
•
Don't import
protects the existing IEDs in case the SCD file does not
match the original configuration in PCM600.
•
Replace unknown
can be used when it is known that the file includes
additional IEDs that are needed. The IED of type “Generic IEC 61850
IED” is used to integrate these kinds of IEDs into, for example, the plant
structure.
•
Ignore PCM Object Type
updates the IED object(s) in PCM600 from the
IED type(s) in the SCD file, discarding whether or not the IED type(s) in
the SCD file matches the IED object(s) in PM600.
•
Ignore Substation Section
does not import the SSD file part of the SCD
file.
4.
Click
Import
when the definition has been completed.
A progress view displays the importing procedure.
7.6
Writing communication configuration to IED
IEC 61850 communication depends on proper communication configuration in all
IEDs that communicate via IEC 61850. It is not possible to read the communication
configuration from the IED to PCM600.
However it is possible to make a configuration change in one IED, without affecting
the communication engineering. For example, when the Application Configuration
1MRS756800 F
Section 7
IEC 61850 communication engineering
630 series
111