2.1. Click in the class field of the signal to change the class configuration.
The
Select Class
window opens.
2.2. Make the selection according to the definitions in the project and click
OK
to close the window and get the new configuration.
IEC08000338-2-en.vsd
IEC08000338 V2 EN
Figure 109:
CMT: Select Class window
9.4.1
Configuring DNP3 class
In DNP3 the user classifies the signals and defines which signals are not a member of
any class. Communication Management tool has a default predefined organization of
classes per signal type. In the master station the classes can be polled in sequences
according to the demands in the project. Unsolicited reporting is possible as well.
Modify the organization of the classes for each signal individually.
1.
Click in the
Class
field of the signal.
The
Select Class
window opens for classifying the signal.
2.
Select the signal classes and choose between
None
and
0
to
3
according to the
project demands.
3.
Click
OK
to set the signal classification.
4.
Write to IED.
1MRS756800 F
Section 9
DNP3 communication engineering
630 series
135
Engineering Manual