IEC symbol name
Node type
IEC symbol
definitions
ANSI Y32.2/
IEEE 315
symbol
definitions
Category
Breaker2 indication only, 00 =
Middle position
35
Switchgear
Breaker2 indication only, 01 =
Open
35
Switchgear
Breaker2 indication only, 10 =
Closed
35
Switchgear
Breaker2 indication only, 11 =
Undefined
35
Switchgear
Static text
0
Texts
Dynamic text
29
Texts
Select button, 00 = Middle
position
30
Texts
Select button, 01 = Open
30
Texts
Select button, 10 = Closed
30
Texts
Select button, 11 = Undefined
30
Texts
Indication button, 00 = Middle
position
31
Texts
Indication button, 01 = Open
31
Texts
Indication button, 10 = Closed
31
Texts
Indication button, 11 =
Undefined
31
Texts
6.2.3
Bay configuration engineering
A page with a single line diagram and measurements contains active living objects.
The object values are updated by the IED periodically (measurement) or in case of an
event. Once the symbols are placed on the HMI page they must be linked to the
corresponding function block in the application configuration, which protects or
controls the object that the symbol on the HMI page represents.
6.2.3.1
Creating a complete HMI display page
1.
Make a sketch how to present the single line diagram.
2.
Place the apparatus, transformer and other symbols that are needed for the single
line diagram into the raster boxes.
3.
Add connection points where needed.
Section 6
1MRS756800 F
Local HMI engineering
96
630 series
Engineering Manual