IEC08000271.vsd
Execution order
group 1
Execution order
group 2
Execution order
group 3
Execution Flow
IEC08000271 V1 EN
Figure 38:
ACT: Concept of Execution order sequence
In the conceptual MainApplication example in
, the execution order of the
main function block in the execution order group 2 defines the execution orders
needed in group 1 and 3. The preceding logic done with function blocks in group 1
must have a lower execution order than the ones in group 2. The following function
blocks in group 3 must have a higher execution order than the main function block in
group 2.
5.1.4
Configuration parameters
Configuration parameters can be viewed and set with the Parameter Setting tool. For
example, the SMAI function block has to be configured to support AC-current values
or AC-voltage values.
5.1.5
Connections and variables
A connection is the link or "wire" between function block outputs and inputs.
Rules and methods to do connections:
•
Drag a line between two signals.
•
Link two signals by using variables.
It is possible to search and replace variable names in ACT.
Connection validation
Only signals of same type can be connected, see
.
Section 5
1MRS756800 F
Protection and control engineering
60
630 series
Engineering Manual