Table 378:
HZCCCSPVC Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm output
6.2.8
Settings
Table 379:
HZCCASPVC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Start value
1.0...100.0
%In
0.1
10.0
Start value, percentage of the nominal
current
Alarm delay time
100...300000
ms
10
3000
Alarm delay time
Alarm output mode
1=Non-latched
3=Lockout
3=Lockout
Select the operation mode for alarm
output
Table 380:
HZCCASPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Measurement mode
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Table 381:
HZCCBSPVC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Start value
1.0...100.0
%In
0.1
10.0
Start value, percentage of the nominal
current
Alarm delay time
100...300000
ms
10
3000
Alarm delay time
Alarm output mode
1=Non-latched
3=Lockout
3=Lockout
Select the operation mode for alarm
output
Table 382:
HZCCBSPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Measurement mode
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Section 6
1MRS757454 D
Supervision functions
344
611 series
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......