5.2.6
Signals
Table 339:
CCBRBRF Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
Io
SIGNAL
0
Residual current
BLOCK
BOOLEAN
0=False
Block CBFP operation
START
BOOLEAN
0=False
CBFP start command
POSCLOSE
BOOLEAN
0=False
CB in closed position
CB_FAULT
BOOLEAN
0=False
CB faulty and unable to trip
Table 340:
CCBRBRF Output signals
Name
Type
Description
CB_FAULT_AL
BOOLEAN
Delayed CB failure alarm
TRBU
BOOLEAN
Backup trip
TRRET
BOOLEAN
Retrip
5.2.7
Settings
Table 341:
CCBRBRF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Current value
0.05...2.00
xIn
0.05
0.30
Operating phase current
Current value Res
0.05...2.00
xIn
0.05
0.30
Operating residual current
CB failure trip mode
1=2 out of 4
2=1 out of 3
3=1 out of 4
2=1 out of 3
Backup trip current check mode
CB failure mode
1=Current
2=Breaker status
3=Both
1=Current
Operating mode of function
CB fail retrip mode
1=Off
2=Without Check
3=Current check
1=Off
Operating mode of retrip logic
Retrip time
0...60000
ms
10
120
Delay timer for retrip
CB failure delay
0...60000
ms
10
240
Delay timer for backup trip
Section 5
1MRS757454 D
Protection related functions
316
611 series
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......