Table 497:
Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
Front
TCP/IP
protocol
Standard Ethernet CAT 5 cable with RJ-45
connector
10 MBits/s
Rear
TCP/IP
protocol
Shielded twisted pair CAT 5e cable with
RJ-45 connector or fiber optic cable with LC
connector
100 MBits/s
Table 498:
Serial rear interface
Type
Counter connector
Serial port (X5)
10-pin counter connector Weidmüller BL
3.5/10/180F AU OR BEDR
or
9-pin counter connector Weidmüller BL
3.5/9/180F AU OR BEDR
1)
Serial port (X16)
9-pin D-sub connector DE-9
1) Depending on the optional communication module
Table 499:
Fiber optic communication link
Connector
Fiber type
Wave length
Typical max.
length
1)
Permitted path attenuation
2)
LC
MM 62.5/125 or
50/125 μm glass
fiber core
1300 nm
2 km
<8 dB
1) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors
in the path.
2) Maximum allowed attenuation caused by connectors and cable together
Table 500:
IRIG-B
Description
Value
IRIG time code format
B004, B005
1)
Isolation
500V 1 min
Modulation
Unmodulated
Logic level
5 V TTL
Current consumption
<4 mA
Power consumption
<20 mW
1) According to the 200-04 IRIG standard
Table 501:
Degree of protection of flush-mounted protection relay
Description
Value
Front side
IP 54
Rear side, connection terminals
IP 20
Section 12
1MRS757454 D
Technical data
514
611 series
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......