4.4.4.9
Monitored data
Table 262:
MNSPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
T_ENARESTART
INT32
0...10000
s
Estimated time to reset of
block restart
MNSPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.4.4.10
Technical data
Table 263:
MNSPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
Minimum
Typical
Maximum
I
Fault
= 2.0 × set
Start
value
23
25 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Negative-sequence current before = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3)
Start value multiples in range of 1.10...5.00
4.4.4.11
Technical revision history
Table 264:
MNSPTOC Technical revision history
Technical revision
Change
B
Internal improvement
C
Internal improvement
1MRS757454 D
Section 4
Protection functions
611 series
251
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......