4.5.1.8
Settings
Table 269:
PHPTOV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...1.60
xUn
0.01
1.10
Start value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
40...300000
ms
10
40
Operate delay time
Operating curve type
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
15=IEC Def. Time
Selection of time delay curve type
Table 270:
PHPTOV Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve
1=Immediate
2=Def time reset
1=Immediate
Selection of reset curve type
Type of time reset
1=Freeze Op timer
2=Decrease Op
timer
1=Freeze Op timer Selection of time reset
Table 271:
PHPTOV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for operate
activation
Curve parameter A
0.005...200.000
1
1.000
Parameter A for customer programmable
curve
Curve parameter B
0.50...100.00
1
1.00
Parameter B for customer programmable
curve
Curve parameter C
0.0...1.0
1
0.0
Parameter C for customer programmable
curve
Curve parameter D
0.000...60.000
1
0.000
Parameter D for customer programmable
curve
Curve parameter E
0.000...3.000
1
1.000
Parameter E for customer programmable
curve
Voltage selection
1=phase-to-earth
2=phase-to-phase
2=phase-to-phase
Parameter to select phase or phase-to-
phase voltages
Section 4
1MRS757454 D
Protection functions
258
611 series
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......