5.1.6
Signals
Table 331:
INRPHAR Input signals
Name
Type
Default
Description
I_2H_A
SIGNAL
0
Second harmonic phase A current
I_1H_A
SIGNAL
0
Fundamental frequency phase A current
I_2H_B
SIGNAL
0
Second harmonic phase B current
I_1H_B
SIGNAL
0
Fundamental frequency phase B current
I_2H_C
SIGNAL
0
Second harmonic phase C current
I_1H_C
SIGNAL
0
Fundamental frequency phase C current
BLOCK
BOOLEAN
0=False
Block input status
Table 332:
INRPHAR Output signals
Name
Type
Description
BLK2H
BOOLEAN
Second harmonic based block
5.1.7
Settings
Table 333:
INRPHAR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
5...100
%
1
20
Ratio of the 2. to the 1. harmonic leading
to restraint
Operate delay time
20...60000
ms
1
20
Operate delay time
Table 334:
INRPHAR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 335:
INRPHAR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
5.1.8
Monitored data
Table 336:
INRPHAR Monitored data
Name
Type
Values (Range)
Unit
Description
INRPHAR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 5
1MRS757454 D
Protection related functions
306
611 series
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......