Figure 174:
Complex power and power quadrants
Table 400:
Power quadrants
Quadrant
Current
P
Q
PF
Power
Q1
Lagging
+
+
0…+1.00
+ind
Q2
Lagging
-
+
0…-1.00
-cap
Q3
Leading
-
-
0…-1.00
-ind
Q4
Leading
+
-
0…+1.00
+cap
The active power P direction can be selected between forward and reverse with
Active
power Dir
and correspondingly the reactive power Q direction can be selected with
Reactive power Dir
. This affects also the accumulated energy directions.
The accumulated energy is calculated separately as forward active (
EA_FWD_ACM
),
reverse active (
EA_RV_ACM
), forward reactive (
ER_FWD_ACM
) and reverse reactive
(
ER_RV_ACM
). Depending on the value of the unit multiplier selected with
Energy
unit Mult
, the calculated power values are presented in units of kWh/kVArh or in units
of MWh/MVArh.
When the energy counter reaches its defined maximum value, the counter value is
reset and restarted from zero. Changing the value of the
Energy unit Mult
setting resets
the accumulated energy values to the initial values, that is,
EA_FWD_ACM
to
Forward
Wh Initial
,
EA_RV_ACM
to
Reverse Wh Initial
,
ER_FWD_ACM
to
Forward VArh
Initial
and
ER_RV_ACM
to
Reverse VArh Initial
. It is also possible to reset the
accumulated energy to initial values through a parameter or with the
RSTACM
input.
Section 7
1MRS757454 D
Measurement functions
358
611 series
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......