remains active for the time set with the
Trip pulse time
setting or until the
values of all the phase currents or residual currents drop below the
Current
value
and
Current value Res
setting respectively, whichever takes longer.
•
If
CB failure trip mode
is set to "2 out of 4", the failure detection requires
that a phase current and a residual current both exceed the
Current value
and
Current value Res
setting respectively or two phase currents exceeding
the
Current value
. Once
TRBU
is activated, it remains active for the time set
with the
Trip pulse time
setting or until the values of all the phase currents
drop below the
Current value
, whichever takes longer.
In most applications, "1 out of 3" is sufficient.
•
If the
CB failure mode
is set to "Breaker status", the
TRBU
output is activated if
the circuit breaker is in the closed position. Once activated, the
TRBU
output
remains active for the time set with the
Trip pulse time
setting or the time the
circuit breaker is in the closed position, whichever is longer.
•
If the
CB failure mode
setting is set to "Both",
TRBU
is activated when the
"Breaker status" or "Current" mode conditions are satisfied.
The activation of the
BLOCK
input deactivates the
TRBU
output.
1MRS757454 D
Section 5
Protection related functions
611 series
313
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......