xii
I.L. 40-386.4
REL301 and 302 Version 1.12
FEATURES ADDED AND IMPROVEMENTS MADE TO VERSION 1.11
1.
REL301 and 302
1.1
Changed 3Vo sensitivity from 3 volts to 1 volt for the directional units in order to increase
the sensitivity for zone-2 and zone-3.
1.2
Changed the loss of current blocking (“LOI Blk”) timer from 0.5/0.5 to 10/0.5 seconds in
order to prevent blocking of zone-2 ground distance, zone-3 ground distance for settings
of “T2G” and/or “T3G” are greater than 0.5 seconds and ground backup tripping longer
than 0.5 seconds.
1.3
Improved the loss of potential blocking logic by removing the lead between LOP Timer (8/
0) output and AND1G.
1.4
Corrected the angle display for the 1-amp ct application. Now, the angle display is extend-
ed from 50% to 10% of the ct rating.
1.5
Extended the front communication access time from 2 to 15 minutes after depressing the
front push-button.
1.6
Redefined the programmable contact output signals LLT & TBM to IM & IOM, respective-
ly.
1.7
Corrected a software error for the operation of the programmable output contact OC-3.
1.8
Corrected the LV setting for the use of the programmable output contacts. The output
contacts of LV should be picked up if any one of the voltages fall below the LV setting. In
version 1.11, the normally open contacts closed if any one of the voltages exceeded the
LV setting.
1.9
Improved the accuracy of the programmable contact outputs (PCO) pickup and dropout
timers.
1.10
Improved the accuracy of 3-phase distance tripping by removing KI0 compensation which
was incorrectly applied to this calculation.
1.11
Corrected LED and Man-Machine Interface targeting mismatch. LED could indicate incor-
rect fault type for certain trip operations.
2.
REL302
2.1
Changed the RDOG timer from 16/0 to 33/0 ms. For a 3-phase fault at 0% location, the
RDOG may pick up momentarily and may start the TBM (carrier keying); therefore, it may
delay the pilot trip action.
NOTE: For the pilot application, the setting of FDGT should be greater than 3 cycles.
2.2
Removed reclose initiate output from weakfeed trip logic.
Содержание REL 301
Страница 15: ......
Страница 24: ...I L 40 386 4 1 10 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL301 302 Layout Vertical ...
Страница 26: ......
Страница 27: ......
Страница 55: ...I L 40 386 4 2 27 Figure 2 8 Zone 1 Extension Scheme Figure 2 7 Zone 3 Trip Logic 1503B49 Sub 2 9662A64 Sub 1 ...
Страница 67: ...I L 40 386 4 2 39 Figure 2 31 REL302 Reversible Zone 3 Phase and Ground Reverse Block Logic 1503B55 Sub 2 ...
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 91: ......