I.L. 40-386.4
4-2
1. Contact rating information see Section 1.6
CONNECTION SPECIFICATION CHART
Location
Notes
ANALOG INPUTS
See Figure 4-2
Voltages and Currents
SIGNAL INPUTS
Non-Pilot Connection
52a
52b
EXT RESET
Pilot Connection REL 302
(Add Following
Connections)
PLT ENA
RCVR1
RCVR2
Reclosing/Sync-check
HOLD
EXT.RI
RECLOSE LOCKOUT
Terminals TB4-3 (+), TB4-4 (-)
Terminals TB4-5 (+), TB4-6 (-)
Terminals TB4-7 (+), TB4-8 (-)
Terminals TB4-9 (+), TB4-10 (-)
Terminals TB4-11 (+), TB4-12 (-)
Terminals TB4-13 (+), TB4-14 (-)
Terminals TB5-7 (+), TB5-8 (-)
Terminals TB5-9 (+), TB5-10 (-)
Terminals TB4-1 (+), TB4-2 (-)
52a required for some reclosing applications or programma-
ble logic.
52b contact required for some logic functions.
External Reset - resets LEDs and erases protection targets.
85CO input required for pilot logic operation.
Channel 1 receiver input.
Channel 2 receiver input 3-term.
Stops reclosing cycle.
Begin (initiates) reclosing cycle.
Drives reclosing cycle to lockout.
CONTACT OUTPUTS
Trip Connection
TRIP A1
TRIP A2
Terminals TB1-4, FT-6
Terminals TB1-3, FT-7
Isolated TRIP 1, switched by FT-6
Isolated Trip 2, switched by FT-7
Basic System Connections
OC1
SYS TEST
BFI/RI ENA
RI-1
RI-2
RB1
RB2
OC3
BFIA-1
BFIA-2
OC2
OC4
OC5/STOP
GS
AL-1
AL-2
Terminals TB1-2, FT-8
Terminal TB1-1
Breaker Failure Initiate/Reclose Initiate
Terminals TB3-1, TB3-2
Terminals TB3-3, TB3-4
Terminals TB3-5, TB3-6
Terminals TB3-7, TB3-8
Terminals TB3-11, TB3-12
Terminals TB3-13, TB3-14
Terminals TB3-15, TB3-16
Terminals TB3-17, TB3-18
Terminals TB3-19, TB3-20
Terminals TB3-21, TB3-22
Terminals TB3-23, TB3-24
Terminals TB3-15, TB3-26
Terminals TB3-27, TB3-28
Trip rated
1
programmable contact
Jumper connected to FT-5, required to power BFI/I enable
function.
Enabled/Disabled by FT-5.*
Isolated Reclose Initiate, (FT-5*)
Isolated Reclose Initiate, (FT-5*)
Isolated Reclose Block, (FT-5*)
Isolated Reclose Block, (FT-5*)
Non-trip rated
1
programmable output contact.
Isolated Breaker Failure Initiate, (FT-5*)
Isolated Breaker Failure Initiate, (FT-5*)
Non-trip rated
1
programmable output contact.
Non-trip rated
1
programmable output contact.
Non-trip rated
1
programmable output contact.
General Start, closes for any disturbance detection
Isolated Failure Alarm
Isolated Relay Trip Alarm
Pilot Connection
(Add following
Connections)
SEND
STOP
Terminals TB3-9, TB3-10
Terminals TB3-21, TB3-22
Pilot Channel Equipment Start
Pilot Channel Equipment Stop (Programmed Stop Function)
Reclosing/Sync-check
CLOSE-1
CLOSE-2
LOCKOUT
FAIL RECLOSE
IN PROGRESS
(Optional)
Terminals TB2-1, TB2-2
Terminals TB2-3, TB2-4
Terminals TB5-1, TB5-2
Terminals TB5-3, TB5-4
Terminals TB5-5, TB5-7
Isolated Close Contact #1
Isolated Close Contact #2
Alarm for Lockout State
Programmable Output for Failed Reclose State/Sync Status
Programmable Output for Reclose in Progress/Sync Status
Communication
Connection:
See Sections 4.6 and 4.7
Содержание REL 301
Страница 15: ......
Страница 24: ...I L 40 386 4 1 10 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL301 302 Layout Vertical ...
Страница 26: ......
Страница 27: ......
Страница 55: ...I L 40 386 4 2 27 Figure 2 8 Zone 1 Extension Scheme Figure 2 7 Zone 3 Trip Logic 1503B49 Sub 2 9662A64 Sub 1 ...
Страница 67: ...I L 40 386 4 2 39 Figure 2 31 REL302 Reversible Zone 3 Phase and Ground Reverse Block Logic 1503B55 Sub 2 ...
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 91: ......