I.L. 40-386.1
5-12
The following inputs can be tested, in the “TEST” mode, By applying voltage to each input and
observing the “Inputs” display. Scroll to the “Inputs” display, apply rated voltage and as each
input is energized, the associated display segment changes from “–” to “|”.
This completes the REL 301 and REL 302 (non-pilot) Acceptance Test.
5. 2.
PILOT ACCEPTANCE TESTS (FOR REL 302 ONLY)
5.2.1
Non-Pilot Acceptance Tests for REL 301/302
Perform the acceptance test procedures in Section 5.1 if not previously completed. These tests
are valid tests of hardware and firmware performance for either REL 301 or REL 302.
5.2.2
Input Opto-Coupler Check
STEP 12
Pilot Enable (PLT ENA)
In Step 3, Section 5.1, the settings from Table 5-5 should have been loaded for Non-Pilot Ac-
ceptance Tests. Change the following settings using the procedure in Step 4 above:
“Pilot”
=
“YES” (Enable pilot logic)
“SystType”
=
“Blocking” (Pilot system selection setting)
“Pilot Ø”
=
“4.5 Ohms” (Pilot phase distance reach setting)
“Pilot G”
=
“4.5 Ohms” (Pilot ground distance reach setting)
“Dir Type”
=
“Zero sequence” (Directional overcurrent polarization choice setting)
“GB Type”
=
“Disabled” (Overcurrent ground backup curve family setting)
Test Using Blocking System
Apply an AG fault as described in Step 6 above. The REL 302 should
not trip.
Apply rated dc voltage to terminals T
B
4-9(+) and T
B
4-10(-). Again apply an AG fault as de-
scribed in Step 6 above. When the relay trips, remove the fault current.
PILOT and AG LED’s
will light. The LCD display will switch to the “L-FLT” mode and fault distance will be displayed.
Using the R
AISE
and L
OWER
push-buttons the complete fault record can be reviewed. See Table
4-3 for a description of the displayed fault data quantities.
Input Under Test
Display
“52a”
|- - - - -
“52b”
- | - - - -
“EXT RESET”
- - | - - -
“PLT ENA” (Pilot Enable, REL 302 only)
- - - | - -
“RCVR1” (Receiver 1, REL 302 only)
- - - - | -
“RCVR2” (Receiver 2, REL 302 only)
- - - - - |
Содержание REL 301
Страница 15: ......
Страница 24: ...I L 40 386 4 1 10 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL301 302 Layout Vertical ...
Страница 26: ......
Страница 27: ......
Страница 55: ...I L 40 386 4 2 27 Figure 2 8 Zone 1 Extension Scheme Figure 2 7 Zone 3 Trip Logic 1503B49 Sub 2 9662A64 Sub 1 ...
Страница 67: ...I L 40 386 4 2 39 Figure 2 31 REL302 Reversible Zone 3 Phase and Ground Reverse Block Logic 1503B55 Sub 2 ...
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 91: ......