I.L. 40-386.1
5-1
PURPOSE
The purpose of this procedure is to provide a test that can be used for incoming inspection or
to determine at any time if the REL 301 or 302 is functioning correctly. The Acceptance Test
confirms that a particular unit is serviceable with a minimum of time and effort. During the Ac-
ceptance Test the emphasis is on hardware verification.
If the reader’s goal is to completely evaluate REL 301 and/or REL 302 firmware, the Engineer-
ing Evaluation Test Manual is recommended for that purpose. The manual is intended to aid
the user in understanding the software design and/or decide if the REL 301 or REL 302 is suit-
able for a specific application. For further details see Engineering Evaluation Test Manual, TM
40-386.
The Acceptance Test Will Cover:
• Front Panel, Man-Machine-Interface (MMI) test
Self test relay status display
Metering mode display test
Settings application
• Hardware Verification
• Impedance Accuracy Check
• Tests of all inputs and contact outputs
• Additionally, if the relay under test is a REL 302, the pilot logic and pilot distance measuring
function will be tested.
Test Equipment:
The minimum test equipment required is:
• One 3-phase, variable (magnitude and phase angle), Y-connected voltage source
• One 1-phase, variable (magnitude and phase angle), current source synchronized to the volt-
age source
• Two Flexitest (FT) test plugs
• Appropriate test leads and hand tools
The test equipment can be in the form of popular multi-function test equipment, such as the
equipment offered by AVO International Multi-Amp, Doble Engineering Company or Powertec
Industries Inc., or by using conventional phase shifter, load box, various test setups.
!
CAUTION
Before energizing the relay it is extremely important to check that all jumpers on the
filter, power supply and microprocessor modules are in the correct position.
Section 5. REL 301/302 ACCEPTANCE TEST
AND PERIODIC MAINTENANCE PROCEDURES
Содержание REL 301
Страница 15: ......
Страница 24: ...I L 40 386 4 1 10 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL301 302 Layout Vertical ...
Страница 26: ......
Страница 27: ......
Страница 55: ...I L 40 386 4 2 27 Figure 2 8 Zone 1 Extension Scheme Figure 2 7 Zone 3 Trip Logic 1503B49 Sub 2 9662A64 Sub 1 ...
Страница 67: ...I L 40 386 4 2 39 Figure 2 31 REL302 Reversible Zone 3 Phase and Ground Reverse Block Logic 1503B55 Sub 2 ...
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 91: ......