I.L. 40-386.1
5-10
Again apply an AG fault. Again the
Zone 1 and AG LEDs will light and begin flashing. The LCD
display will switch to the “L-FLT” mode and fault distance will be displayed. Apply rated dc volt-
age to terminals TB4-7(+) and TB4-8(-). The LCD will display “FLT Type”, all fault data will be
erased and the LED’s will stop flashing. Remove the voltage from TB4-7 and TB4-8.
STEP 9
52b Input
Using the MMI change the setting of “CIF Trip” from “No” to “Yes” using the procedure in Step
4 above. Apply an AG fault as described in Step 6 above, except with a current of 2 Amp at an
angle of 75
°
lagging the fault voltage. The relay should
not trip.
Apply rated dc voltage to terminals TB4-5(+) and TB4-6(-). Again apply an AG fault with a cur-
rent of 2 Amp at an angle of 75
°
lagging the fault voltage. The relay should trip and a review of
the target should show “CIF Trip” “Yes”. Remove the voltage from TB4-5 and TB4-6. Change
the setting of “CIF Trip” from “Yes” to “No”.
5.1.6
Input Transformer (Ip) Check
STEP 10
Change the following settings using the procedure in Step 3 above.
“Zone 1Ø”
=
“Disabled” (Zone 1 phase distance setting)
“Zone 1G”
=
“Disabled” (Zone 1 ground distance setting)
“Dir Type”
=
“Dual Polariz.” (Directional overcurrent polarization choice setting)
“GB Type”
=
“CO-8” (Overcurrent ground backup curve family setting)
“GBPickup”
=
“0.5 Amps” (Overcurrent ground backup pickup setting)
“GBTCurve”
=
“24” (Overcurrent ground backup curve selection setting)
“GB Dir”
=
“YES” (Overcurrent ground backup directional choice setting)
Since the “GB Dir” = “YES”, the Ground Backup logic is directional, torque controlled and is
supervised by Forward Directional Overcurrent Ground (FDOG) logic. In order to test the direc-
tional logic, 3Ø voltages must be applied for correct directional reference. With no voltage ap-
plied or if the setting of Loss -of-Potential Block (“LOP Blk”) is “Yes” and at least one input
voltage is zero volts, GB will be non-directional regardless of the GB Dir setting.
This test is to verify the dual polarizing or fourth current transformer input (Ip). For a dual polar-
izing ground directional unit test, connect the test circuit shown in Figure 5-7. Apply I
P
= 1.0A
∠
-90
°
to terminals F
T
-13 (+) and F
T
-12 (-), and apply a balanced 3-phase voltage (V
a
= V
b
= V
c
= 70 Vac). Apply I
A
= 4A to terminals F
T
-15 (+) and F
T
-16 (-) to the system under test. Vary the
angle of I
A
relative to I
p
and observe tripping at all of the following angles of I
A
:
• All angles between -3
°
and -177
°
• Or -90
° ±
87
°
, where -90
°
could be referred to as the maximum torque angle
When the relay trips, remove the fault current.
OTHER and AG LEDs will light. The LCD display
will indicate the fault distance. Using the R
AISE
and L
OWER
push-buttons the complete fault
record can be reviewed. See Table 4-3 for a description of the displayed fault data.
Содержание REL 301
Страница 15: ......
Страница 24: ...I L 40 386 4 1 10 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL301 302 Layout Vertical ...
Страница 26: ......
Страница 27: ......
Страница 55: ...I L 40 386 4 2 27 Figure 2 8 Zone 1 Extension Scheme Figure 2 7 Zone 3 Trip Logic 1503B49 Sub 2 9662A64 Sub 1 ...
Страница 67: ...I L 40 386 4 2 39 Figure 2 31 REL302 Reversible Zone 3 Phase and Ground Reverse Block Logic 1503B55 Sub 2 ...
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 91: ......