Figure 16:
Captured synchrophasor data
9.5.2
Verifying the IEEE C37.118/1344 UDP communication
GUID-F0D1117D-3D0F-498F-A00C-242763F8A4E6 v1
After setting both PMU configuration and the UDP client configuration (As
explained in sections
Setting the PMU station communication (PMU Report)
Setting the PMU station communication (PMU configuration)
) and making sure that the Ethernet
communication is set up, click
Connect
on the PMU Connection Tester tool.
IEC140000145-1-en.vsd
IEC140000145 V1 EN-US
Figure 17:
Verifying the UDP communication using PMU Connection Tester
•
Now it should be possible to see the streaming synchrophasor data.
•
Verify the communication by following the same steps as in section
the IEEE C37.118/1344 TCP communication
1MRK 505 378-UEN A
Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Line differential protection RED670 2.2 IEC
85
Commissioning manual