Check that this value is equal to:
(
)
injected
injected
injected
injected
L
L
xy
cp
U
U
U
U
I
j
j
R
jX
X
X
=
-
-
+
×
+
æ
ö
ç
÷
è
ø
Completing the test
Continue to test another function or end the test by changing the
TESTMODE
setting to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
11.11.7.3
Sudden change in current variation SCCVPTOC
GUID-5494DF56-449D-49BE-B75D-9C667E890E16 v1
Prepare the IED for verification of settings as outlined in section
and section
1.
Set
Operation
to
On
.
2.
Connect the test set for three-phase current injection to the appropriate IED
terminals.
3.
Inject symmetrical phase currents equal to half the rated current.
4.
Increase the injected current in phase L1 slowly by more than the set
I>
. No
signal shall be activated.
5.
Decrease the injected current in phase L1 to half the rated current.
6.
Increase the injected current in phase L1 in a step by more than the set
I>
.
Start and trip signal shall be activated.
11.11.7.4
Carrier receive logic LCCRPTRC
GUID-16B24935-A9F4-427C-9B8D-71B25DE000E2 v1
Prepare the IED for verification of settings as outlined in section
and section
1.
Set
Operation
to
On
.
2.
Select
OpMode
according to the application: If two carrier channels are used
and high security shall be used set
OpMode
=
2 Out Of 2
, otherwise
1 Out Of
2
.
3.
Connect switchable binary signal/s CR1 and CR2 to the binary input/s to be
used for the carrier receive (CR) signal/s.
4.
Connect switchable binary signal/s to the binary input to be used for the local
check signal. If three pole trip is used only one LOCTR is used. If single pole
trip is used in addition the phase selective signals LOCTRL1, LOCTRL2and
LOCTRL3 are connected.
5.
Connect switchable binary signal/s to the binary input to be used for the
communication supervision signal/s CHERR1 and CHERR2.
If
OpMode
=
2 Out Of 2
:
6.
Activate input and check output signals according to table
.
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
250
Line differential protection RED670 2.2 IEC
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...