Table 39:
Activate input signals if OpMode = 2 Out Of 2
INPut
CR1
X
X
X
X
X
X
CHERR1
X
CR2
X
X
X
X
X
CHERR2
X
LOCTR
X
X
X
LOCTRL1
X
LOCTRL2
X
LOCTRL3
X
Table 40:
Activate output signals if OpMode = 2 Out Of 2
OUTPut
Non
X
X
TRIP
X
X
X
X
X
TRL1
X
TRL2
X
TRL3
X
7.
Connect the trip output to a timer.
8.
Have inputs CR1and CR2 activated. Start the timer from activation of input
LOCTR and stop the timer from TRIP output.
9.
Check the trip time.
If
OpMode
=
1 Out Of 2
:
10. Activate input and check output signals according to table
Table 41:
Activate input signals if OpMode = 1 Out Of 2
INPut
CR1
X
X
X
X
X
CHERR1
X
CR2
X
X
X
X
X
X
CHERR2
LOCTR
X
X
X
LOCTRL1
X
X
LOCTRL2
X
X
LOCTRL3
X
X
1MRK 505 378-UEN A
Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC
251
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...