1.
Check that the input logical signals BLOCK, CBOPEN and VTSU are logical
zero.
2.
Supply a three-phase rated voltage in all three phases and note on the local
HMI that the TRIP logical signal is equal to the logical 0.
3.
Switch off the voltage in all three phases.
After set
tTrip
time a TRIP signal appears on the corresponding binary output
or on the local HMI.
Note that TRIP at this time is a pulse signal, duration should
be according to set
tPulse
.
4.
Inject the measured voltages at rated values for at least set
tRestore
time.
5.
Activate the CBOPEN binary input.
6.
Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
7.
Inject the measured voltages at rated values for at least set
tRestore
time.
8.
Activate the VTSU binary input.
9.
Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
10. Reset the VTSU binary input.
11. Inject the measured voltages at rated values for at least set
tRestore
time.
12. Activate the BLOCK binary input.
13. Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
14. Reset the BLOCK binary input.
11.6.6.2
Completing the test
SEMOD175023-47 v4
Continue to test another function or end the test by changing the
TESTMODE
setting to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
11.6.7
Radial feeder protection PAPGAPC
GUID-1A9BA2F9-7AFB-4C27-B851-55E0E9DC4D03 v1
The Signal Monitoring tool in PCM600 shows the service values that are available
on the Local HMI as well.
11.6.7.1
Verifying the settings
GUID-302BE312-2BF8-48C9-9914-A96F16984980 v1
Values of the logical signals for PAPGAPC are available on the local HMI under:
Main menu/Tests/Function status/Voltage protection/RadialFeeder(27, U<)/
PAPGAPC(27, U<):1
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
206
Line differential protection RED670 2.2 IEC
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...