To verify the mho characteristic, at least two points should be tested.
In the following, three test points are proposed. The mho characteristic always goes
through the origin, which automatically gives a fourth point for the characteristic.
11.4.3.1
Phase-to-phase faults
M14944-292 v8
ZAngPP
ZPP
1
2
3
Ohm/phase
R
X
IEC07000009-4-en.vsd
50%
IEC07000009 V4 EN-US
Figure 27:
Proposed test points for phase-to-phase fault
Table 24:
Test points for phase-to-phase (ohms / phase)
Test
points
reach
Value
Comments
1
X
ZPP · sin(ZAngPP)
R
ZPP · sin(ZAngPP)
2
X
0,5· (ZPP· sin(ZAngPP)
R
0,5·ZPP + ΔR = 0,5·ZPP·(1+cos(ZAngPP))
3
X
0,5·ZPP·sin(ZAngPP)
R
0,5·ZPP - ΔR = 0,5·ZPP(1-cos(ZAngPP))
Change the magnitude and angle of phase-to-phase voltage to achieve impedances
at test points 1, 2 and 3. For each test point, observe that the output signals,
START, STLx and STPP are activated where x refers to the actual phase to be
tested. After the timer
tPP
for the actual zone has elapsed, also the signals TRIP,
TRPP and TRx shall be activated.
11.4.3.2
Phase-to-earth faults
M14944-393 v7
For simplicity, the same test points as for phase-to-phase faults are proposed, but
considering new impedance values.
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
122
Line differential protection RED670 2.2 IEC
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...