![ABB RED670 Relion 670 series Скачать руководство пользователя страница 290](http://html.mh-extra.com/html/abb/red670-relion-670-series/red670-relion-670-series_commissioning-manual_3169290.webp)
Indicated result
Possible reason
Proposed action
ADC-module OK
No problem detected.
None.
ADC-module Fail
The AD conversion
module has failed.
Contact your ABB representative for service.
(Protocol name) Ready
No problem detected.
None.
(Protocol name) Fail
Protocol has failed.
(I/O module name)
Ready
No problem detected.
None.
(I/O module name) Fail
I/O modules has failed.
Check that the I/O module has been
configured and connected to the IOP1-
block.
If the problem persists, contact your ABB
representative for service.
14.2
Fault tracing
IP8765-1 v1
14.2.1
Internal fault indications
M11763-2 v5
If an internal fault has occurred, the local HMI displays information under
Main
menu/Diagnostics/IED status/General
Under the Diagnostics menus, indications of a possible internal failure (serious
fault) or internal warning (minor problem) are listed.
Indications regarding the faulty unit are outlined in table
Table 45:
Self-supervision signals on the local HMI
HMI Signal Name:
Status
Description
INT Fail
OFF / ON
This signal will be active if one or more
of the following internal signals are
active; INT--LMDERROR, INT--
WATCHDOG, INT--APPERROR, INT--
RTEERROR, or any of the HW
dependent signals
INT Warning
OFF / ON
This signal will be active if one or more
of the following internal signals are
active; INT--RTCERROR, INT--
IEC61850ERROR, INT--
TIMESYNCHERROR
ADMnn
READY / FAIL
Analog input module n failed. Signal
activation will reset the IED
BIMnn
READY / FAIL
BIM error. Binary input module Error
status. Signal activation will reset the
IED
BOMn
READY / FAIL
BOM error. Binary output module Error
status.
IOMn
READY / FAIL
IOM-error. Input/Output Module Error
status.
MIMn
READY / FAIL
mA input module MIM1 failed. Signal
activation will reset the IED
Table continues on next page
Section 14
1MRK 505 378-UEN A
Troubleshooting
284
Line differential protection RED670 2.2 IEC
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...