Values of logical signals for SSIMG protection are available on the local HMI
under
Main menu/Tests/Function status/Monitoring/InsulationGas(63)/
SSIMG(63):x
, where x = 1, 2,....21.
The Signal Monitoring in PCM600 shows the same signals that are available on the
local HMI.
Check that the input logical signal
BLOCK
is logical zero and that on the local
HMI, the logical signals
PRESALM
,
PRESLO
,
TEMPALM
,
TEMPLO
,
ALARM
and
LOCKOUT
are logical zero.
11.13.1.1
Testing the gas medium supervision for pressure alarm and pressure
lockout conditions
GUID-768DAAC8-F89D-4401-B86D-9B26FD7224F6 v3
1.
Connect binary inputs to consider gas pressure and gas density to initiate the
alarms.
2.
Consider the analogue pressure input
SENPRES
and set
SENPRES
to a value
lower than
PresAlmLimit
or activate binary input signal
SENPRESALM
, check
that outputs
PRESALM
and
ALARM
are activated after a set time delay of
tPressureAlarm
.
3.
Gas pressure lockout input
SETPLO
can be used to set
PRESLO
.
4.
Also, reduce further the pressure level input below
PresLOLimit
or activate
the binary input signal
SENPRESLO
, check that
PRESLO
signal appears after
a set time delay of
tPressureLO
.
5.
Activate
BLOCK
binary input and check that the outputs
PRESALM
,
PRESLO
,
ALARM
and
LOCKOUT
disappear.
6.
Reset the
BLOCK
binary input.
7.
Make sure that pressure lockout condition exists and then activate the reset
lock out input
RESETLO
and check that the outputs
PRESLO
and
LOCKOUT
reset.
11.13.1.2
Testing the gas medium supervision for temperature alarm and
temperature lock out conditions
GUID-EC145626-90B0-45A2-AD58-CB8BF203FE16 v1
1.
Consider the analogue temperature input
SENTEMP
and set
SENTEMP
to a
value higher than
TempAlarmLimit
, check that outputs
TEMPALM
and
ALARM
are activated after a set time delay of
tTempAlarm
.
2.
Temperature lockout input
SETTLO
can be used to set
TEMPLO
signal.
3.
Also, increase further the temperature input above
TempLOLimit
, check that
the outputs
TEMPLO
and
LOCKOUT
appears after a set time delay of
tTempLockOut
.
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
260
Line differential protection RED670 2.2 IEC
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...