WaterMaster
Electromagnetic flowmeter
2 Parameter Tables
IM/WMPBST–EN Rev. B
7
56 / 40
DIAG_ALARM_SIMULATION
Selects the device alarm to simulate.
0: Off
2: Logic simulation selected on OP1
3: Pulse simulation selected on OP1
4: Logic simulation selected on OP1
5: Pulse simulation selected on OP2
6: Logic simulation selected on OP3
7: Low flow alarm
8: High flow alarm
9: Q > 103% Qmax
10: Simulation mode on
11: Tx. simulator / calibrator mode
12: At Qmax, volume display overrun <1600hrs
13: Totalizer reset
14: Intermittent sensor comms
16: Tx. memory fault detected
17: Sensor memory not detected
18: Tx. measurement suspended
19: Empty pipe
20: Open circuit electrode
21: Short circuit electrode
22: Installation fault/condition
23: Open circuit coil/wiring
24: Short circuit coil/wiring
25: Check cable+coil resistance
26: Transmitter hardware fault
27: Bad flow data
28: Accuracy warning?
29: OIML self-check limits exceeded
30: Measurement starting
32: Sensor setup not complete
33: Incompatible sensor
34: Tx. code memory fault
35: Tx. data memory fault
37: Non-volatile summary alarm
Unsigned 8
1
D
r,w / C / a
Off
57 / 41
CLEAR_ALARM_HISTORY
Clears the alarm history in the device.
Unsigned 8
1
S
r,w / C / a
–
58 / 42
MASK_MAINTENANCE_REQUIRED
Mask for the Maintenance group alarms.
0: Disabled
1: Enabled
Unsigned 8
1
S
r,w / C / a
Disabled
59 / 43
MASK_CHECK_FUNCTION
Mask for the Function Check group alarms.
0: Disabled
1: Enabled
Unsigned 8
1
S
r,w / C / a
Disabled
60 / 44
MASK_OFF_SPECIFICATION
Mask for the Off Specification group alarms.
0: Disabled
1: Enabled
Unsigned 8
1
S
r,w / C / a
Disabled
61 / 45
MASK_MIN_ALARM
Mask for the Min. Flow alarm.
0: Disabled
1: Enabled
Unsigned 8
1
S
r,w / C / a
Enabled
62 / 46
MASK_MAX_ALARM
Mask for the Max. Flow alarm.
0: Disabled
1: Enabled
Unsigned 8
1
S
r,w / C / a
Enabled
Abs. Idx /
Rel. Idx
Variable Name / Brief Description
Data Type
Size
Store
Access /
Usage /
Transport
Default
Table 2.2 Slot 0 – Physical Block (Continued)