WaterMaster
Electromagnetic flowmeter
2 Parameter Tables
26
IM/WMPBST–EN Rev. B
28 / 12
OUT_SCALE
Scale of the Process Variable.
The Function Block parameter OUT_SCALE contains the values of the lower limit and
upper limit effective range, the code number of the engineering unit of Process Variable
and the number of digits on the right hand side of the decimal point.
DS-36
11
S
r,w / C / a
–
29 / 13
LIN_TYPE
Unused, fixed to NO_LINEARISATION.
0: No Linearization
Unsigned 8
1
S
r,w / C / a
No Linearization
30 / 14
CHANNEL
Reference to the active Transducer Block that provides the measurement value to the
Function Block.
0x0521: TB5.ELECTRODE_1_RESISTANCE
0x0539: TB5.ELECTRODE_2_RESISTANCE
0x053A: TB5.BACK_OFF_VOLTAGE
0x053B: TB5.COIL_AND_CABLE_RESISTANCE
0x053C: TB5.COIL_INDUCTANCE
0x053D: TB5.SENSOR_INDUCTANCE_SHIFT
0x053E: TB5.TRANSMITTER_AVERAGE_GAIN_SHIFT
Unsigned 16
2
S
r,w / C / a
TB5.ELECTRODE_
1_
RESISTANCE
31 / 15
UNUSED
Unused parameter.
–
–
–
–
–
32 / 16
PV_FTIME
Filter time of the Process Variable.
The Function Block parameter PV_FTIME contains the time constant for the rise time of
the FB output up to a value of 63.21 % resulted from a jump on the input (PT1 filter). The
engineering unit of the parameter is second.
Float
4
S
r,w / C / a
0
33 / 17
FSAFE_TYPE
Defines the reaction of device, if a fault is detected. The calculated ACTUAL MODE
remains in AUTO.
For mode FSafe Value, the block parameter FSAFE_VALUE is used as OUT and the
status is set to UNCERTAIN_Substitute Value,
In mode Last Stored, the last stored valid OUT value is used as OUT and the status is set
to UNCERTAIN_LastUsableValue. If there is no valid value available, the status is set to
UNCERTAINInital_Value and the OUT value is set to its initial value.
In the mode Out Status Bad, OUT has the wrong calculated value and status is set to
BAD_* (with * as calculated).
0: Fsafe Value
1: Last Stored
2: Out Status Bad
Unsigned 8
1
S
r,w / C / a
Last Stored
34 / 18
FSAFE_VALUE
Default value for the OUT parameter, if a sensor or sensor electronic fault is detected. The
unit of this parameter is the same as that for OUT.
Float
4
S
r,w / C / a
–
35 / 19
ALARM_HYS
Hysteresis value applied to block parameters HI_HI_LIM, HI_LIM, LO_LIM and
LO_LO_LIM. The hysteresis is expressed as value below high limit and above low limit in
the engineering unit of xx_LIM.
Float
4
S
r,w / C / a
–
36 / 20
UNUSED
Unused parameter.
–
–
–
–
–
37 / 21
HI_HI_LIM
Upper limit value for alarms with the same engineering unit as that of the OUT parameter.
If the measured variable is equal to or higher than the upper limit value, the State Bits in
the Status Byte of OUT and in the FB parameter ALARM_SUM change to 1.
Float
4
S
r,w / C / a
–
38 / 22
UNUSED
Unused parameter.
–
–
–
–
–
Abs. Idx /
Rel. Idx
Variable Name / Brief Description
Data Type
Size
Store
Access /
Usage /
Transport
Default
Table 2.8 Slot 6 – Analog Input 4 – Diagnostic Signal (Continued)