WaterMaster
Electromagnetic flowmeter
2 Parameter Tables
30
IM/WMPBST–EN Rev. B
44 / 28
UNUSED
Unused parameter.
–
–
–
–
–
45 / 29
UNUSED
Unused parameter.
–
–
–
–
–
46 / 30
UNUSED
Unused parameter.
–
–
–
–
–
47 / 31
POS_D
The current position of the valve (discrete).
102
2
D
r / C / a
–
48 / 32
SETP_DEVIATION
Difference between set point signal and feedback position in % travel span (between
OPEN and CLOSE position).
Float
4
D
r / C / a
–
49 / 33
CHECK_BACK
Detailed information of the device, bitwise coded. More than one message possible at
once.
OctetString
3
D
r / C / a
–
50 / 34
CHECK_BACK_MASK
Definition of supported CHECK_BACK information bits.
OctetString
3
Cst
r / C / a
–
51 / 35
SIMULATE
For commissioning and maintenance reasons, it is possible to simulate the READBACK
by defining the value and the status. The Transducer Block and the AO-FB are
disconnected when the SIMULATE parameter is in use.
DS-50
6
S
r,w / C / a
–
52 / 36
INCREASE_CLOSE
Direction of positioner in mode RCas and Auto.
Unsigned 8
1
S
r,w / C / a
–
53 / 37
OUT
The process variable of the analog output block in engineering units in AUTO and RCas
mode and is the value specified by the operator/engineer in Man and LO mode.
101
5
D
r,w / C / a
–
54 / 38
OUT_SCALE
Scale of the Process Variable.
The Function Block parameter OUT_SCALE contains the values of the lower limit and
upper limit effective range, the code number of the engineering unit of Process Variable
and the number of digits on the right hand side of the decimal point.
DS-36
11
S
r,w / C / a
–
Abs. Idx /
Rel. Idx
Variable Name / Brief Description
Data Type
Size
Store
Access /
Usage /
Transport
Default
Table 2.9 Slot 7 – Analog Output 1 – Display Value (Continued)