Input/Output / ...Dig.Out 51/52 / ...Alarm Config
General Alarm
Select error messages signaled via the binary output 51 / 52.
Only if the parameter "Logic Output Action" is set to Alarm Signal.
Default setting: Off.
Qv Volumeflow Max
Qv Volumeflow Min
EPD
Menu / parameter
Description
Input/Output / ...Dig.Out 51/52 / ...Setup Logic Output
Logic Output Action
Selection of binary output function.
See description ‘„Input/Output / ...Dig.Out 41/42 / ...Setup Logic Output’.
Active Mode
Select switching properties for the binary output.
• Active High: Normally open.
• Active Low: Normally closed.
7 . . .Operation
. . .Parameter descriptions
Menu: Process Alarm
. . .Menu: Input/output
Menu / parameter
Description
Process Alarm
Alarm history
Display of the alarm history
Clear Alarm History
Reset of the alarm history.
. . .Group Masking
Selection of submenu ‘...
Group Masking
’ using .
. . .Alarm Limits
Selection of submenu ‘...
Alarm Limits
’ using .
Process Alarm / . . .Alarm Limits
Qm Massflow Min
Sets the minimum / maximum limit value (0 ... 110 %) for mass measurement. If the process value "Qm [unit]"
exceeds or falls below the limit value, an alarm is triggered.
Qm Massflow Max
Qv Volumeflow Min
Sets the minimum / maximum limit value (0 ... 110 %) for volume measurement. If the process value "Qv [unit]"
exceeds or falls below the limit value, an alarm is triggered.
Qv Volumeflow Max
Process Alarm / . . .Group Masking
Maintenance Required
Alarm messages are divided into groups.
If masking is activated for a group (On), no alarm is issued.
For further information, see chapter "Diagnosis / error messages" on page 62.
Function Check
Out Of Specification