![ABB ProcessMaster FEM611 Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/abb/processmaster-fem611/processmaster-fem611_operating-instruction_4481024.webp)
24
FEM610 |
PROCESSMASTER | OI/FEM610-EN REV. A
Connection to remote mount design
Flowmeter sensor site
Transmitter side
5 . . .Installation
Note
Use wire end sleeves.
• Wire end sleeves 0.75 mm2 (AWG 19), for shielding (1S,
2S).
• Wire end sleeves 0.5 mm2 (AWG 20), for all other wires.
The shields may not touch (signal short circuit).
8 (
)
0.31
25 (
)
0.98
A
G12025
90 (3.54)
20
(0.8)
70 (2.76)
1
2
3
4
5
7
6
8
9
A
50 (1.97)
70 (2.76)
A
8 (
)
0.31
25 (
)
0.98
A
G12026
1
2
3
4
5
20
(0.8)
Figure 34 Signal Cable Part No . D173D031U01,
Dimensions in inch (mm)
Figure 35 Signal Cable Part No . D173D031U01,
Dimensions in mm (inch)
Pos .
Terminal Function / comments
Color
1
3
Measurement potential
green
2
E1
Signal line
violet
3
1S
Shield for E1
—
4
E2
Signal line
blue
5
2S
Shield for E2
—
6
M2
Magnet coil
red
7
M1
Magnet coil
brown
8
—
Not connected
yellow
—
Not connected
orange
9
SE /
Shield
—
Pos .
Terminal Function / comments
Color
1
3
Measurement potential
green
2
E1
Signal line
violet
3
1S
Shield for E1
—
4
E2
Signal line
blue
5
2S
Shield for E2
—
6
M2
Magnet coil
red
7
M1
Magnet coil
brown
8
—
Not connected
yellow
—
Not connected
orange
9
SE /
Shield
—