50
FEM610 |
PROCESSMASTER | OI/FEM610-EN REV. A
Menu / parameter
Device Setup
. . .Access Control
Selection of submenu ‘...
Access Control
’ using .
. . .Sensor
Selection of submenu ‘...
Sensor
’ using .
. . .Transmitter
Selection of submenu ‘...
Transmitter
’ using .
Device Setup / . . .Sensor
Range Mode Config
Activation of the second measuring range for the mass and volume flow.
The setting can be performed separately for the mass flow rate (Qm) and volume flow (Qv). This means that it
is possible to switch quickly between two measuring ranges (e.g. Qm Max and Qm Max2). Switching is
performed via the parameters "Qm Range Mode", "Qv Range Mode".
• Disabled: Second measuring range for mass and volume flow rate deactivated.
• Qm and Qv: Second measuring range for mass and volume flow rate activated.
• Qm only: Second measuring range for mass flow activated.
• Qv only: Second measuring range for volume flow activated.
Default setting: Disabled
Qm Max DN
The value specifies the lower massflow rate a flow velocity of 32.8 ft/s (10 m/s). The value is set automatically
via the selected nominal size multiplied with the density set.
Qm Max 1
Setting of the upper measuring range value 1 (Measuring range = 0 ... Qm Max 1) for the mass flow for forward
flow and reverse flow. Default setting: 1 x QmaxDN
Qm Max 2
Setting of the upper measuring range value 2 (Measuring range = 0 ... Qm Max 2) for the mass flow for forward
flow and reverse flow. This parameter is only available if the value "Max2 active" has been selected for the
parameter "Qm Range Mode".
Qm Range Mode
Manual switchover between the measuring ranges (Max1 active / Max2 active) for the mass flow
measurement. This parameter is only available if the value Qm only or Qm and Qv has been selected for the
parameter "Range Mode Config".
Qv Max DN
The value specifies the lower volume flowrate rate a flow velocity of 32.8 ft/s (10 m/s). The value is set
automatically via the selected nominal size.
Qv Max 1
Setting of the upper measuring range value 1 (Measuring range = 0 ... Qv Max 1) for the volume flow for
forward flow and reverse flow. Default setting: 1 x QmaxDN
Qv Max 2
Setting of the upper measuring range value 2 (Measuring range = 0 ... Qv Max 2) for the volume flow for
forward flow and reverse flow.
This parameter is only available if the value "Max2 active" has been selected for the parameter "Qv Range
Mode".
Default setting: 1 x QmaxDN
Qv Range Mode
Manual switchover between the measuring ranges (Max1 active / Max2 active) for the volume flow
measurement. This parameter is only available if the value Qv only or Qm and Qv has been selected for the
parameter Range Mode Config".
Sensor Location Tag
Entry of the measuring point tag for the sensor.
Alphanumeric, max. 20 characters
Sensor Tag
Entry of the TAG number of the sensor.
Alphanumeric, max. 20 characters.
. . .Operating Mode
Selection of submenu ‘...
Operating Mode
’ using .
Device Setup / . . .Access Control
Standard Password
Entry / change of the password for the ‘Standard’ access level.
Read Only Switch
Indicator of the position of the write protection switch.
For further information, see chapter "Write protection switch" on page 27.
7 . . .Operation
. . .Parameter descriptions
Menu: Device setup