Installation and commissioning guide
1ZSC000563-ACF EN, REV. A, 2020-06-25
49
4.11 Grounding of the bushing flange
Overview
The bushing flange must be grounded to the transformer tank. This prevents electrical discharge between the
bushing flange and the transformer tank under normal service conditions.
There are two alternatives.
DANGER!
Make sure that the grounding is correct. An unsatisfactory grounding can cause damage to
equipment, or death to personnel.
Procedure with a cone point set screw
1.
Apply a large quantity of Mobilgrease 28 to the
cone point set screw (50).
CAUTION!
The quality of the cone point set screw
is important, stainless steel of A4-80
quality is recommended.
NOTE!
Or use a lubricant similar to
Mobilgrease 28.
G000380
2.
Install the cone point set screw (50).
NOTE!
The cone point of the set screw
penetrates the paint. This makes an
electrical connection between the
bushing and the transformer tank,
keeping them at the same potential.
Torque
M12: 40 Nm
End of instruction
Procedure with a flexible cable
1.
Clean the contact surfaces.
2.
Put a flexible cable (64) between the grounding
hole in the bushing flange and a grounding point
on the transformer.
G000381
Содержание GOE(2)
Страница 76: ...76 Installation and commissioning guide 1ZSC000563 ACF EN REV A 2020 06 25 ...
Страница 78: ......
Страница 79: ......