![ABB GOE(2) Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/abb/goe-2/goe-2_installation-and-commissioning-manual_5362012.webp)
12
Installation and commissioning guide
1ZSC000563-ACF EN, REV. A, 2020-06-25
G000700
A.
Maximum cantilever load at installation angle 0°
B.
Maximum cantilever load at installation angle 30°
C.
Maximum axial static load
D.
Load applied at the midpoint
Type
Test load 1 minute
(N)
Maximum cantilever load in operation
at installation angle (N)
Maximum axial
static load (N)
0°
30°
GOE(2) 1175
10000
5000
4400
20000
GOE(2) 1425
10000
5000
4100
20000
GOE(2) 1550
10000
5000
3900
20000
GOE(2) 1675
10000
5000
3900
20000
Maximum permitted torque on the outer terminal
The maximum torque that is permitted on the outer terminal is 250 Nm.