Technical data
85
3ADW000462R0401 DCS880 Hardware manual e d
Control circuit terminal layout
Internal 24 V
DC
used
External 24 V
DC
used
Relay driver
2k
+24 V
DC
+3.3 V
DC
max. +24 V
DC
DO
DI
100n
DIOGND
2k
+3.3 V
DC
max. +24 V
DC
DI1 ... DI5 and DIL
DI
100n
DICOM
2k
+3.3 V
DC
max. +24 V
DC
DI6
DI
100n
DIOGND
XAI
Reference voltage and analog inputs
1
+VREF
+10
V
DC
2
-VREF -10
V
DC
3
AGND
Common ground (connected to frame)
4
AI1+
±10 V or 0 (4) ... 20 mA depending on J1
5
AI1-
6
AI2+
±10 V or 0 (4) ... 20 mA depending on J2
7
AI2-
8
AI3+ ±10
V
9
AI3-
J1
J1
AI1 current / voltage selection jumper
J2
J2
AI2 current / voltage selection jumper
XAO Analog
outputs
1
AO1
±10 V or 0 (4) ... 20 mA depending on J5
2
AGND
Common ground (connected to frame)
3
AO2 ±10
V
4
AGND
Common ground (connected to frame)
5
IACT
Connection point for a scope (H1 ... H6 only)
c
J5
J5
AO1 current / voltage selection switch
XD2D Drive-to-drive
link
1
B
Drive-to-drive link
2
A
(master-follower or embedded fieldbus)
3
BGND
Isolated ground 2
J3
J3
Drive-to-drive link termination switch
XRO1, XRO2, XRO3 Relay outputs
11 NC
12 COM
250
V
AC
/ 30 V
DC
13 NO
2
A
21 NC
22 COM
250
V
AC
/ 30 V
DC
23 NO
2
A
31 NC
32 COM
250
V
AC
/ 30 V
DC
33 NO
2
A
XD24 Digital
interlock
1
DIL
Digital interlock, ground: DICOM
2
+24VD
+24
V
DC
, 200 mA, ground : DIOGND
3
DICOM
Isolated digital input ground for DI1 ... DI5 and DIL
4
+24VD
+24
V
DC
, 200 mA, ground : DIOGND
5
DIOGND
Isolated digital input / output ground for DI6, DIO1, DIO2
J6
J6
Digital ground selection switch (DIOGND and DICOM)
XDIO
Digital inputs / outputs
1
DIO1
2
DIO2
XDI Digital
inputs
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
XENC Encoder
1
A+
Channel A+ function depending on J4A
2
A-
Channel A- function depending on J4A
3
B+
Channel B+ function depending on J4B
4
B-
Channel B- function depending on J4B
5
Z+
Channel Z+ function depending on J4C
6
Z-
Channel Z- function depending on J4C
7
EGND
Common ground (connected to frame)
8
+VENC
Encoder supply 5 V
DC
or 24 V
DC
depending on J4D, 250 mA
J4A
J4A
Differential or single ended (10 k pull up)
J4B J4B
selection
jumpers
J4C
J4C
J4D
J4D
Encoder supply 5 V
DC
or 24 V
DC
selection jumper
J7A
J7A
Not in use for DCS880
J7B J7B
XTAC
Analog tacho
1
±8 … 270 V
DC
2
AITACH-
XSMC Mains
contactor
1
MCCOM
250 V
AC
/ 30 V
DC
Fixed output for the mains
2
MCNO
2 A contactor
3
STOCOM
250 V
AC
/ 30 V
DC
Fixed output for safe torque
4
STONO
2 A
off (STO) zero current monitor
XSTO
Safe torque off (STO)
1 OUT1 24
V
DC
for STO circuit
2
SGND
Common ground (connected to frame)
3
IN1
Both circuits must be closed for drive to start
4
IN2
Open circuits block the firing pulses
X12
Safety functions module connection
X13
Control panel connection
X205
Memory unit connection
c
For H7 and H8 see SDCS-OPL-H01.
SA_880_005_DCS_d.ai
DCS880
Safety
relais
XD24 Digital
interlock
1
DIL
2
+24VD
3
DICOM
4
+24VD
5
DIOGND
J6 J6
XDIO
Digital input / outputs
1
DIO1
2
DIO2
XDI Digital
inputs
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
Power
supply
PLC
0 V
DC
24 V
DC
SA_880_010_DCT-PLC_a.ai
default
default
OnBoard Encoder
Feedback
7
EGND
24 V
5 V
8
J4D
1 2 3 4 5 6
XENC
+ A -
+ B -
+ Z -
J4
A B C
J4
D
Encoder
supply
10 k
24 V
5 V
120
pull up
differential
1
4
7
3
6
9
10
12