3ADW000462R0401 DCS880 Hardware manual e d
DCSLink communication
The field converter is controlled from armature converter via DCSLink based on CAN hardware.
Node address is set by:
S800 digit 0 (node address 00 is not possible!).
S801 digit 10.
Same node address must be selected in the corresponding armature converter.
Example: Node address = 13 ==> S800 = 3 and S801 = 1.
The communication speed is set by S1100.
RS232-Port
The RS232 interface is used for download the 'Field exciter firmware package'.
The firmware download is activated by setting S2:1-2 before the auxiliary voltage is switched ON.
Field exciter mode is S2:3-4 (default).
S1100:6 S1100:5 S1100:4 Baudrate
[kBaud]
Selection in armature converter,
parameter (94.02)
OFF
OFF
OFF
20
0
OFF
OFF
ON
50
1
OFF
ON OFF
125
2
OFF
ON
ON
250
3
ON
OFF
OFF
500
4
ON
OFF
ON
800
5
ON
ON
OFF
888
6
ON
ON
ON
1000
7
SF_DCF_002_DCSLink_b.ai
X2:
3
SDCS-FEX-
8
1 /
8
2
S1100:1
CANL
CANH
S1100:
3
GNDB
S1100:2
4
5
Termination 200 kOhm
DSL communication
Remarks
Bus termination
S1100:
1 = ON
120 Ohm
1 = OFF
no termination
Ground termination
S1100:
2 = ON
200 kOhm R-C ground termination
3 = ON
0 Ohm ground termination
2, 3 = OFF
no termination
S800
S801
Switch_0-9.dsf