Technical data
98
3ADW000462R0401 DCS880 Hardware manual e d
Chaining a PC via a control panel
This figure shows how to chain a PC via a control panel to several drives.
Note:
When a control panel is used for a PC connection, it cannot be used to operate the drives.
Setting up the firmware
1.
Power up the unit.
2.
Set the node ID, see 49.01 Node ID number. All
drives
connected to the panel bus must have a unique
node ID. It is advisable to reserve node ID 1 for spare / replacement
drives
, because they have node ID 1
as the default setting.
3.
Set the baud rate, see 49.03 Baud rate. The baud rate has to be the same for all nodes on the panel bus.
4.
Select a suitable communication loss action, see 49.04 Communication loss time and 49.05
Communication loss action.
5.
Save the settings with 49.06 Refresh settings = Refresh.
Note:
Refreshing may cause a communication break, thus reconnecting the
drives
may be required.
SB_880_003_DPI-H_b.ai
Unit 1
(49.01 = 1)
X10:2
…
X10:1
X10:2 X10:1
X10:2 X10:1
S100 = OFF
S101 = OFF
Unit 2
(49.01 = 2)
S100 = OFF
S101 = OFF
Unit n (max. 32)
(49.01 = n)
S100 = ON
S101 = OFF
1)
The control panel terminates the bus at its end, so only the other end
of the bus must be terminated.
1)
SDCS-DPI-H01
SDCS-DPI-H01
SDCS-DPI-H01