Electrical installation
71
3ADW000462R0401 DCS880 Hardware manual e d
The maximum distance between pulse encoder and SDCS-CON-H01 dependents on the voltage
drop of the connecting lines and on the output and input configuration of the used components. Use
cables according to the table below. Use twisted pair cables with pair shielding plus overall shielding.
Cable length
Parallel wires for
power source & GND
Cable used
0 ... 50 m
1 x 0.25 mm²
12 x 0.25 mm²
50 ... 100 m
2 x 0.25 mm²
12 x 0.25 mm²
100 ... 150 m
3 x 0.25 mm²
14 x 0.25 mm²
Cable length
Parallel wires for
power source & GND
Cable used
0 ... 164 ft
1 x 24 AWG
12 x 24 AWG
164 ... 328 ft
2 x 24 AWG
12 x 24 AWG
328 ... 492 ft
3 x 24 AWG
14 x 24 AWG
1k0
4k7
1k0
4k7
+5V
121
W
100 nF
10k
+5V
0V
+5V or +24V
XENC:1
XENC:2
XENC:7
XENC:8
3
2
1
J4A
SS_880_005_encoder_b.ai
ENCODER CHANNEL
A
Differential
SDCS
-CON-H01
ENCODER INPUT
A
Jumper settings for differential encoders connected to
SDCS-CON-H01
Jumper
SDCS-CON-H01
J4A
J4B
J4C
1 - 2
4 - 5
7 - 8
1 - 2
4 - 5
7 - 8
Differential
J4D
5 V:
10 - 11
24 V:
11 - 12
Voltage
source