Planning the electrical installation
45
3ADW000462R0401 DCS880 Hardware manual e d
EMC filters (E1)
Filter in a grounded line (earthed TN or TT network)
The filters are suitable for grounded lines only, for example in public European 400 V
AC
lines.
According to EN 61800-3 filters are not needed in insulated industrial networks with own supply
transformers. Furthermore they could cause safety risks in such floating lines (IT networks).
According to EN 61800-3 filters are not needed in industrial zone (Second Environment) for DCS880
drives above 100 A
DC
rated current. For rated currents below 100 A
DC
the filter requirement is
identical to Light Industry (First Environment).
Three-phase filters
EMC filters are necessary to fulfil the standard for emitted interference if a converter shall be run at a
public low voltage line, in Europe for example with 400 V
AC
. Such lines have a grounded neutral
conductor. ABB offers suitable three-phase filters for 400 V
AC
. For 440 V
AC
public low voltage lines
outside Europe 500 V
AC
filters are available. Optimize the filters for the real motor currents:
I
Filter
= 0.8 • I
MOT max
; the factor 0.8 respects the current ripple.
Lines with 500 V
AC
up to 1000 V
AC
are not public. They are local networks inside factories, and they
do not supply sensitive electronics. Therefore, converters do not need EMC filters if they shall run
with 500 V
AC
and more.
EMC f
ilter on request.
Size
Converter type (2-Q)
I
DC
[A] Converter type (4-Q)
I
DC
[A]
Filter type
for D = 4
Filter type
for D = 5
H1 DCS880-S01-0020-0d
20
DCS880-S02-0025-0d
25
NF3-440-25
NF3-500-25
DCS880-S01-0045-0d
45
DCS880-S02-0050-0d
50
NF3-440-50
NF3-500-50
DCS880-S01-0065-0d
65
DCS880-S02-0075-0d
75
NF3-440-64
NF3-500-64
DCS880-S01-0090-0d
90
DCS880-S02-0100-0d
100
NF3-440-80
NF3-500-80
H2 DCS880-S01-0135-0d
135
DCS880-S02-0150-0d
150
NF3-440-110
NF3-500-110
DCS880-S01-0180-0d
180
DCS880-S02-0200-0d
200
NF3-500-320
NF3-500-320
DCS880-S01-0225-0d
225
DCS880-S02-0250-0d
250
NF3-500-320
NF3-500-320
DCS880-S01-0270-0d
270
DCS880-S02-0300-0d
300
NF3-500-320
NF3-500-320
H3 DCS880-S01-0315-0d
315
DCS880-S02-0350-0d
350
NF3-500-320
NF3-500-320
DCS880-S01-0405-0d
405
DCS880-S02-0450-0d
450
NF3-500-600
NF3-500-600
DCS880-S01-0470-0d
470
DCS880-S02-0520-0d
520
NF3-500-600
NF3-500-600
H4 DCS880-S01-0610-0d
610
DCS880-S02-0680-0d
680A
NF3-500-600 NF3-500-600
DCS880-S01-0740-0d
740
—
—
NF3-500-600 NF3-500-600
— —
DCS880-S02-0820-0d
820
NF3-690-1000
NF3-690-1000
DCS880-S01-0900-0d
900
DCS880-S02-1000-0d
1000
NF3-690-1000
NF3-690-1000
H5
DCS880-S01-1190-0d
1190
DCS880-S02-1190-0d
1190
NF3-690-1000
NF3-690-1000
H6 DCS880-S01-0900-0d
900
DCS880-S02-0900-0d
900
NF3-690-1000
NF3-690-1000
DCS880-S01-1200-0d
1200
DCS880-S02-1200-0d
1200
NF3-690-1000
NF3-690-1000
DCS880-S01-1500-0d
1500
DCS880-S02-1500-0d
1500
NF3-690-1600
NF3-690-1600
DCS880-S01-2000-0d
2000
DCS880-S02-2000-0d
2000
NF3-690-1600
NF3-690-1600
H7
3000
3000 NF3-690-2500
NF3-690-2500