Page 36
© 2021 ABB. All rights reserved.
CP:S6000_External Distribution_IG
Rev. 1.3
Controller
LED
(Note 3)
User
Interface Display
Rectifier LEDs
(Note 4)
AC
DC
ALM
Distribution
Module
Board LED
Possible Problem(s)
Possible Solution(s)
AMBER
MIN, Thermal
Probe Fail
Battery thermal probe
failed.
1.
Ensure thermal probe is properly
connected to thermal probe cable.
2.
Ensure cable is properly connected
to the rear of the Distribution
Module.
3.
If problem persists, replace
thermal probe per ensuing
instructions.
4.
If problem still persists, call your
local field representative.
AMBER
MIN, Rectifier Fail
Single rectifier thermal
alarm: Excessive ambient
temperature Multiple
rectifier failure
1.
Verify that there is no obstruction
of the vertical airflow path.
2.
Reset the rectifier by removing the
rectifier, waiting approximately 30
seconds, and replacing the
rectifier.
3.
If problem persists, replace the
rectifier.
4.
If problem still persists, call your
local field representative.
AMBER
MIN, Minor
Communication
Fail
(Single Rectifier
signaling)
-
R
-
Rectifier lost
communication with
controller.
1.
If a rectifier has been removed
from an installed/operational
system, go to the Control/
Operations menu and execute
Uninstall Equipment.
2.
Reset the rectifier by removing the
rectifier, waiting approximately 30
seconds, and replacing.
3.
If problem persists, replace the
rectifier.
4.
If problem still persists, call your
local field representative.
Содержание CPS6000-Systems-48V DC Power
Страница 44: ...Page 44 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Status Menu ...
Страница 46: ...Page 46 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Configuration Menu part 1 ...
Страница 47: ...Page 47 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Configuration Menu part 2 ...
Страница 51: ...Page 51 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 ...