Page 17
© 2021 ABB. All rights reserved.
CP:S6000_External Distribution_IG
Rev. 1.3
Battery String and DC Load Connections
The system has up to 52 bullet
-
style distribution positions. All positions in the initial distribution
panel are selectable between either battery inputs or load outputs. If the system is equipped with a
low voltage load disconnect LVLD, then all load positions are connected to the system through the
LVLD. If the system is equipped with a low voltage battery disconnect LVBD, then all battery positions
are connected to the system through the LVBD. Breaker sizes up to 250A, TPS fuses to 70A and GMT
fuses to 12A are available bullet modules for this system. DC Connections are made with double hole
lugs on ¼
-
20 studs on
5/8”
centers. The maximum tongue width for breaker connections is
0.68”.
Adapter buses are available for larger cables. Notice the color coding in the distribution. Bus bars with
brown labeling are returns. Bus Bar with blue labeling are
-
48V. Labels are provided to identify battery
verses load positions on the ID label on the front door. The initial distribution panel with the controller
is rated for 600A. The supplemental (upper) panel is rated for 300A. Load distribution in system
accordingly.
Note: Yellow handle or black handle Bullet
-
style circuit breakers can be mounted as load or battery
connectors.
Figure 6: Selectable DC Distribution
Number of Conduits
Conduit Size
Number of Rectifiers
per
ac feed
Min External
ac
Breaker
Wire Gage
Number of Wires
in
Conduit
1 per 4
-
slot rectifier shelf
¾ inch
20A
10
40A
1 per 6
-
slot rectifier shelf
1 inch
20A
10
13
40A
60A
Yellow handle circuit breakers
Send alarm in manual off or trip position; mid
-
trip breakers
Black handle circuit breakers
Send alarm only in tripped position
Table 3: AC Wire and Protectors for 50A rectifiers
Содержание CPS6000-Systems-48V DC Power
Страница 44: ...Page 44 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Status Menu ...
Страница 46: ...Page 46 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Configuration Menu part 1 ...
Страница 47: ...Page 47 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Configuration Menu part 2 ...
Страница 51: ...Page 51 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 ...