Systems
Weights
19”
23”
1 Distribution/1 Rectifier Shelf
41 lbs
54 lbs
2 Distribution/1 Rectifier Shelf
59 lbs
77 lbs
1 Distribution/2 Rectifier Shelf
55 lbs
74 lbs
2 Distribution/2 Rectifier Shelf
74 lbs
97 lbs
DC Reference (CO) Ground and Chassis Ground
Use a
1/4”
diameter double
-
hole lug on
5/8”
center (Not provided) to ground the chassis as shown in
the figure below. Torque connection to 65 in
-
lbs. The DC reference ground is connected to the return
bus as shown below. Use a
3/8”
diameter double
-
hole lug on
1”
centers (Not provided).
Figure 5: DC Reference Ground and Chassis Ground Connections