Step
Configuration Attribute to
Change
Menu Path/Action
Float Voltage
From the default screen,
press the
Display Menu
key
to see the Main Menu.
4.
Press the down arrow key
until
Configuration
is
highlighted, press the
Display Menu
key and the
following selections are
available; Float settings,
Shunt rating, Rectifier
Redundancy, Batteries,
Contactors, Boost, System
Settings, and
Communication Ports.
The
Float Settings
option
will be highlighted, press
the
Display Menu
key to
access the Float Settings
Menu.
The
Set Point
option will be highlighted. Press the
Display Menu
key to view or change the Float voltage Set
Point. Use the left and right arrow keys to adjust the
Set Point
voltage. Once
the Voltage has been set to the desired value Press the
Display Menu
key to save the change. The voltage
range is 42.0 to 56.5 Volts. Factory default is
-
54.5V.
Select Voltage Alarms to set the four Voltage Alarm thresholds.