Page 10
© 2021 ABB. All rights reserved.
CP:S6000_External Distribution_IG
Rev. 1.3
Rectifier Specifications
The following constant
-
power, vertical airflow rectifiers are available for order with this system.
Values listed are per rectifier. Maximum Heat Dissipation numbers are calculated at 175VAC and
maximum DC voltage and current values for the rectifier.
Figure 2: Typical Rectifier Numbering
Model
Number of Rec-
tifier
Max DC
Current (Idc))
Nominal DC
Voltage (Vdc)
DC
Voltage (Vdc)
Range
AC Voltage (Vac)
Range
Nominal AC
Current (A)
Max BTU/hr
Max Watts
QS861A
15A
48
42
-
58
85
-
150
7.8
450
132
48
42
-
58
150
-
275
4.4
445
130
QS852A
20A
48
42
-
58
150
-
275
6
454
133
QS853A
25A
48
42
-
58
150
-
275
7.4
724
212
QS862A
25/30A
48
42
-
58
85
-
150
12.0
604
177
48
42
-
58
150
-
275
8.8
724
212
QS864A
40A
48
42
-
58
150
-
275
11.8
819
240
QS865A
50A
48
42
-
58
150
-
275
14.5
911
267
Table 1: Rectifier Specifications
Содержание CPS6000-Systems-48V DC Power
Страница 44: ...Page 44 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Status Menu ...
Страница 46: ...Page 46 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Configuration Menu part 1 ...
Страница 47: ...Page 47 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 Configuration Menu part 2 ...
Страница 51: ...Page 51 2021 ABB All rights reserved CP S6000_External Distribution_IG Rev 1 3 ...