Page 16
© 2021 ABB. All rights reserved.
CP:S6000_External Distribution_IG
Rev. 1.3
AC connection is typically 1
-
inch conduit
per rectifier shelf connected on either
the left or right side.
Two sets of conduit ground studs are
located on either side of the box. These
¼
”
studs accept two
-
hole ground lugs on
¾
”
centers.
One, two or three rectifiers may be fed
from a single ac feed using jumpers be-
tween the blocks. Attach jumpers as
shown below. Torque screw to 10 in
-
lbs
AC feed per rectifier
(no jumpers)
AC per two rectifiers
(1 jumper per 2 blocks)
AC per three rectifiers
(2 jumpers between 3 blocks)
If feeding 3 positions, At-
tach wire to center block.
Terminal Blocks in 2U AC Box
L1 connections
L2 connections