INPUTS AND OUTPUTS
The
CBXi-8R8(-H)
,
FLX-8R8
and
FLX-8R8-H
have identical I/O capabilities
–
each has a set of 8 Universal
Inputs and a set of 8 UniPuts
™
with relay.
FLX-4R4
and
FLX-4R4-H
have 4 Universal Inputs and 4 UniPuts with relay.
FLX-16DI
has 16 Digital Inputs only.
Any of the terminals can be configured as inputs. Any of the
UniPut
terminals can be configured as an output.
INPUT MODES
Universal Input
terminals and
UniPut™
terminals can be configured as inputs in almost identical fashion:
Measurement
Mode
Universal Input
UniPut™ as Input:
Digital
Input
Resistance
Resistance measurement
Range:
0 ... 450 kΩ
Accuracy:
±0.5% of measured resistance
-
Temperature measurement
Range: -40 °C ... +110 °C
Accuracy:
10k NTC sensors (e.g. 10k Type 2 (10K3A1) or 10k Type 3
(10K4A1): ±0.3 °C, -40 to 90 °C (-40°F to 194°F); ±0.4 °C > 90 °C (194°F)
-
Digital Volt-Free contact, 2 mA contact-wetting current
Pulse counting (volt-free)
up to 20 Hz, 25 ms
–
25 ms
-
-
24 V AC Detect
-
Voltage
Analog Input
Range: 0 ... 10 V
@
130 kΩ
Accuracy: ±0.5% full
scale [50mV]
Analog Input
Range: 0 ... 10 V
@
40 kΩ
Accuracy: ±0.5% full
scale [50mV]
-
Pulse counting (0 … 10 V) up to 20 Hz, 25 ms –
25 ms
-
Current
Current input
Range: 0 ... 20 mA
@ 390 Ω
Accuracy: ±0.5% full
scale [100μA]
Current input
Range: 0 ... 20 mA
@ 390 Ω
Note: Current Input requires
user-supplied external 390
Ω
resistance.
Accuracy: depends
on user supplied
external resistor
-
Note
: Inputs use on-board 16-bit analog to digital convertor.
Note
: All inputs and outputs are protected against short circuit, as well as over-voltage up to 24 V AC.
Hardware point numbers for these inputs in the
CBXi-8R8(-H)
's
strategy:
CBXi
FLX
address
1
FLX
address
2
FLX
address
3
FLX
address
4
FLX
address
5
Inputs
1
…
8
101
…
108
201
…
208
301
…
308
401
…
408
501
…
508
Outputs
9
…
16
109
…
116
209
…
216
309
…
316
409
…
416
509
…
516