CBXi IP Controller |
CBXi Operation
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
63
MAN
01
41
re
v 2
3
6
CBXi Operation
PHYSICAL LAYOUT
DIMENSIONS
WIRING
CAUTION - DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY
REPLACED.
REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED
BY THE MANUFACTURER. DISPOSE OF USED BATTERIES ACCORDING TO
THE MANUFACTURER'S INSTRUCTIONS.
Supply Requirements
24 V AC ±20 % 50/60 Hz
Supply Rating
CBXi
30 VA (no FLX modules)
CBXi + 1 x FLX
42 VA
CBXi + 2 x FLX
54 VA
CBXi + 3 x FLX
66 VA
FLX Power Connection
Proprietary FLX bus connector
carries power and comms from
CBXi-8R8 unit. CBX-8R8 can supply
power to up to 3 FLX modules.
Auxiliary Power
18 V DC / 60 mA output
BACnet Loading
¼ unit load device
Ground
Common
Point Numbers
Terminal
Numbers
Relay Common
(24 V only)