Set the
Device ID
in the
BACnet
>
Device
page, and optionally set a
Device Name
:
Note:
Device ID
is the
BACnet
device instance number. Every
BACnet
controller within the site must receive a
unique
BACnet
instance number to ensure proper communications. This
BACnet
instance number
should be unique even across subnets. By default, it is set is set to the entire numeric portion of the
Controller's serial number.
If the
CBXi
device is to act as a
BBMD
(allowing
BACnet
communication between
Ethernet
subnets), enter
the relevant parameters on the
BBMD/NAT
page: (see
BACnet IP Broadcast Management Device (BBMD)