CBXi IP Controller |
CBXi Operation
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
70
MAN
01
41
re
v 2
3
AUXILIARY POWER OUTPUTS
The
CBXi
and
FLX
modules each have two 18 V DC outputs, for I/O devices that require loop power.
For 3-wire connections return can be through any COM terminal, but it is recommended that Auxiliary
power wiring is through terminal 14, the COM between the two Auxiliary power terminals.
The DC output terminals provide a minimum of 18 V DC, but the combined load (on each IO module) must
remain below 60 mA.
USING A KEYPAD WITH THE CBXi
A
CBT-STAT
or
UCU Room Display
keypad can be connected to the
CBX
at the CBT-STAT port.
Note
: If
UCU Room Display
is used, refer to the
DS0064 UCU10FC/K
for the corresponding Strategy Point
Setup.