CONNECT THE CBXi-8R8(-H) TO FLX UNITS
The I/O capabilities of a
CBXi-8R8(-H)
can be extended by the addition of
FLX-8R8
and
FLX-8R8-H
devices.
These are connected to the
CBXi-8R8(-H)
by means of a standard module interconnector (
FLX bus
connector)
, one of which is shipped with each
FLX
device.
SET THE FLX ADDRESS
Each of the
FLX
units connected to a single
CBXi
must have an address that is unique on that
CBXi
’s FLX
bus. The address is set by the 5-way DIP switch.
The terminals on a
FLX
unit will be accessible within the CBX Strategy with point numbers prefixed by
this address as illustrated below:
Inter-module bus
Address
DIP switch
setting
Point numbers
00001
1
101 … 116
00010
2
201 … 216
00011
3
301 … 316
Note
: If there are 2 devices on the same
FLX bus
with the same address
–
including
0
, the address of the
CBXi
-
then the bottom (yellow) status LED will blink slowly to indicate a FLX bus address clash