OUTPUT MODES
UniPut
terminals can generate an output as follows:
•
Analog Output 0 ... 10 V, 20 mA, 12-bit resolution
•
Digital Output 0 ... 10 V, 20 mA
•
Relay Contacts with ability to switch up to 24 V AC
Maximum Load: 24 V AC, 2 (1) A resistive (inductive) for all relay contacts
Analog 0 … 10 V output mode
In
Analog 0 ... 10 V output
Mode, the
Uniputs
configure themselves like
this:
where the D/A is the digital to analog converter. All circuitry is fully
protected against 24 V AC.
Digital 0 … 10 V output mode
In
Digital 0 ... 10 V output
Mode, the
Uniputs
configure in the same way
as for analog:
In this mode the output toggles between the voltages defined as
“
ON
” and
“
OFF
”.
Relay Mode
In Relay mode the
Uniputs
are configured with a
single relay common for each half of the
terminals: