CBXi IP Controller |
CBXi Operation
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
64
MAN
01
41
re
v 2
3
TERMINALS
Terminal
Numbers
Description
93, 94
24 V AC Power
13 … 15
Auxiliary Power: 18 V DC output on 2 terminals, 60 mA total
95, 96
RS-485 Port 1 (BACnet® MS/TP) screw terminal
MS/TP subnet terminator switch is located beside the port. If the
switch is towards the icon, then termination is
in
and if the switch is
towards the icon then termination is
out
.
39 … 42
CBT-STAT / RS-485 Port 2 (CBT-STAT / Modbus)
The bus Terminator Switch is located beside the port. If the switch is
towards the icon, then termination is
in
and if the switch is towards
the icon then termination is
out
.
1 … 12
Universal Inputs
When input is configured as Digital:
•
LED Off: open circuit or logic 'off'
•
LED On: logic 'on'
When input is configured as Resistor/thermistor:
•
LED Off: valid resistance connected (Note: 0
Ω
is counted as valid)
•
LED Slow blink: resistor/thermistor not connected
When input is configured as Analog:
•
LED intensity is modulated by the analog signal
When the LED is blinking:
•
Fast blink indicates error condition
•
Two short flashes followed by a value* indicates the input is in an
override state (overridden by
CXpro
HD
).
*
Note
: The LED intensity illustrates the value measured at the input
terminals. The flash indicates that this value has been overridden.
25 … 38
UniPuts™ + Relay
When a Uniput channel is configured as an input, the LED signals are
identical to Universal Inputs above. When configured as an output the
following apply:
When output is configured as Digital:
•
LED Off: open circuit or logic 'off'
•
LED On: logic 'on'
When output is configured as Analog:
•
LED intensity is modulated by the analog signal
When the LED is blinking:
•
Fast blink indicates error condition
•
Two short flashes followed by a value indicates the output is in an
override state (overridden by
CXpro
HD
or HOA).